DB3 / XB11

DB3 / XB11

This range of audio/visual combination units may be assembled from Cooper MEDC’s range of beacons and sounders. Mounted on a sturdy, drilled, painted, stainless steel plate, the units are pre-wired as standard such that a single input operates both the sounder and beacon simultaneously.

Units are available for use in potentially explosive atmospheres and dedicated units are now available for use in industrial and marine environments.

Data Sheets
DB3/XB11 (123 KB) (PDF)
Schematics / Wiring
Download file (73 KB) (PDF)
Certification

ATEX: Ex II 2GD, ExdIIBT5.

IECEx 

  UL: Class I, Div. 1, Groups C & D.
Area Classification Model dependant - refer to datasheet
Voltage 24V d.c., 110V a.c., 240V a.c.
Beacon Standard: XB11 (Xenon 5J).
  Option: Filament (10W). Flourescent (≤10W).
Sounder Standard: DB3 (long flare) ≤115dBA at 1 metre.
  Option: DB3 (short flflare) ≤108dBA at 1 metre.
Dimensions (mm) 420 (height) x 220 (width) x 337 (depth).
Options Refer to data sheet. Specify when ordering.

 

Features

  • Zones 1, 2 and safe area use*.
  • ATEX approved Ex II 2GD*.
  • UL listed Class I, Div. 1 & 2, Groups C & D*.
  • IP66 and IP67.
  • Certified temperature: –55°C to +70°C*.
  • Corrosion free GRP beacon/sounder.
  • Beacon available as xenon, filament or fluorescent.
  • Xenon: up to 21J.
  • Filament: up to 100W.
  • Fluorescent: up to 39W.
  • Sounder: up to 115dBA output at 1 metre.
  • All stainless steel (316), epoxy painted back plate.

*Model dependent.